§ 47-7. Tanks; composition and gauge.  


Latest version.
  • Oil for use in connection with fuel-oil heating apparatus shall be kept or stored in tight tanks, constructed of galvanized steel, basic open-hearth steel or wrought iron of a minimum gauge United States standard, as follows:
    Capacity in gallons
    Gauge
    1 to 285
    14
    286 to 560
    12
    561 to 1,100
    10
    1,101 to 4,000
    3/16-inch
    4,000 to 12,000
    1/4-inch
    12,001 to 20,000
    5/16-inch
    20,001 to 30,000
    3/8-inch